1. Drill the hole according to the cutout chart (see Figure 1). 

    Ceiling thickness should be between 5–10mm.


MIR-HE300


2. Choose an installation location based on detection range and room layout.


3. Turn off the power. Pull wires through the hole, strip6–8mm, 

    And connect to the sensor wires (no polarity).


4. Squeeze the spring clips, insert and rotate the sensor into the ceiling hole, 

    Ensuring it is centered and flush. To remove, squeeze the trim and rotate outward.


MIR-HE300

Note: Always turn off the power before installing, removing, or checking the sensor.


Technical Specifications

Wireless Type

KNX / Zigbee 3.0

Communication Range

80 metres (line of sight)

Radar Application Type

Occupancy / Absence

Radar Transmission Frequency

24 GHz

Detection Angle

Approx. 70°

Illuminance Range

1–1000 lux (tolerance ±20% lux)

Infrared Detection Range

Maximum diameter of approx. 4 metres within the specified installation area

Operating Temperature

10° C to +55° C

Operating Voltage

AC 220V

Product Dimensions

Φ82 × 48 mm